DUCTSIZE PROGRAM OVERVIEWThe Elite Software DUCTSIZE Program quickly calculates optimal duct sizes using either the static regain, equal friction, or constant velocity method. The calculated duct sizes can be printed on a round, rectangular, and flat oval basis. Noise levels and required attenuation are printed for each runout duct. A library of fan data for noise calculations is built into the program. Additionally, a bill of materials with both labor and material costs can be printed. DUCTSIZE allows up to 500 duct sections, and is suitable for both constant volume and VAV systems as diversity is accounted for. Input data is entered using convenient "fill in the blank" screens. Optionally, input data can be taken directly from a duct drawing file created in AutoCAD by the Softdesk HVAC drawing system. DUCTSIZE also has an option for specifying duct height and width constraints to control sizes. This feature is also useful for analyzing problems in existing systems where the duct sizes are already specified. THREE VERSIONS AVAILABLEThe DUCTSIZE Program can be obtained in three forms: demo, equal friction only, and static regain. The static regain version of DUCTSIZE costs $495, and it provides three sizing methods: static regain, equal friction, and constant velocity. The equal friction version of the program costs $295, and it provides two methods of sizing: equal friction and constant velocity. For more information on the demo version please read DEMONSTRATION DISKS below DEMONSTRATION DISKSIf you would like to evaluate the DUCTSIZE program in further detail you can download a demonstration copy from our website, or order a copy, with complete documentation. The demonstration copies retain all the functionality of the full programs, they are just limited on the size of the project data that can be entered. Please follow this link for a description of the demonstration limits for the DUCTSIZE program. SYSTEM REQUIREMENTSDUCTSIZE requires an IBM compatible computer with at least 512K of memory and the PCDOS/MSDOS operating system. The computer must have either two floppy disk drives or one hard disk drive and a floppy drive. |
DUCTSIZE FEATURES
CALCULATION METHODThe DUCTSIZE Program is based on the design procedures given in the 1993 ASHRAE Handbook of Fundamentals and the 1981 SMACNA HVAC Systems Duct Design manual. The program can calculate using either the static regain, equal friction, or constant velocity methods. The user's manual gives detailed information on the exact equations used, and explains how to manually verify program results. PROGRAM INPUTThe DUCTSIZE program uses full screen editing features that provide a simple "fill in the blank" input procedure. All input data is checked at the time of entry so that no improper data can be entered. If you have a question about what the program is requesting, you can press the "?" key which allows the program to offer additional explanations about the input data being requested. Upon completion of the input process, all data is saved to disk and can be reviewed and edited whenever desired. Four types of data are requested: general project data, system and fan data, trunk data, and runout data. The general project data includes the project name, location, client name, duct material, desired sizing method, and more. The fan system data includes the fan type, minimum and maximum allowable air velocities, desired noise levels and more. The trunk and runout data includes such information as duct length, connection numbers, material type, insulation R-values, fitting quantities, runout cfm values, and any duct height and width constraints. Input sheets are provided for the easy data entry. PROGRAM OUTPUTThe DUCTSIZE Program provides four basic output reports: general project data, trunk and runout sizing information, noise analysis, and a bill of materials with complete cost data. In addition to these reports, the built-in library data for duct materials, fans, fittings, and costs can be printed. |
YOUR COMPANY NAME PROJECT: SAMPLE RUN YOUR COMPANY TYPE CLIENT: JOHN DOE ENTERPRISES CITY, STATE DATE: TODAY'S DATE DUCTSIZING CALCULATIONS PROGRAM DESIGNER: W. W. SMITH PROJECT & DEFAULT DATA: TRUNKS RUNOUTS MAXIMUM DESIRED VELOCITY (FT/MIN): 3000 1000 MATERIAL REFERENCE NUMBER: 1 1 HEIGHT CONSTRAINT (IN): 0 0 WIDTH CONSTRAINT (IN): 0 0 DIAMETER CONSTRAINT (IN): 0 0 R-VALUE OF INSULATION (SQ.FT.HR.F/BTU): 4 2 DUCT SHAPE: RECT. ROUND NC-CRITERIA (dB re 0.2 NANOBAR): N/A 35 DESIGN METHOD: 3 2 DUCT SYSTEM DATA: MAXIMUM SYSTEM VELOCITY (FT/MIN): 3000 MINIMUM SYSTEM VELOCITY (FT/MIN): 500 MINIMUM TRUNK DIAMETER (IN): 8 ORIFICE OPENING INTERVAL (IN): 1 TEMPERATURE OF AIR LEAVING COIL: (F) 55 DESIGN ROOM TEMPERATURE: (F) 70 TEMPERATURE OF DUCT INSTALLATION SPACE: (F) 80 ALTITUDE (FEET): 1000 FRICTION LOSS PER 100 FT. (IN. W.G.): 0.100 EST. ST. PRESS. LOSS OF CENTRAL EQUIP. (IN W.G.): 0.850 MAXIMUM % SUPPLY AIR INCREASE: 10 LOSS COEFFICIENT FOR 45 DEGREE ELBOWS: 0.150 LOSS COEFFICIENT FOR 90 DEGREE ELBOWS: 0.350 LOSS COEFFICIENT FOR FIRE DAMPER: 0.170 ALLOW INCREASING DOWNSTREAM DIAMETERS: YES FAN DATA: FAN DESCRIPTION: CENTRIFUGAL AIRFOIL FAN TYPE: 3 FAN STATIC PRESSURE: 0.000 FAN CFM: 0 FAN EFFICIENCY: 85 FAN RPM: 800 NUMBER OF BLADES: 40
******* DUCTSIZE DESIGN PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC ******* YOUR COMPANY NAME CITY, STATE SAMPLE RUN TODAY'S DATE PAGE 2 ************************** DUCTSIZE OUTPUT DATA ************************* TRUNK OUTPUT DATA: -------- LOSSES -------- SECTION SECTION CUMUL. PRESS. TRK# 45 DIA LEN L/100 REG. COEF1 FITTING DYNAMIC VEL PR VELOC. UPS# 90 HEI VEL REF# GAU. COEF2 ADDITL. FRICTN. STATIC STATIC -SM- FD WID CFM MAT. DESCRIPTION DYNAMIC TOTAL TOTAL TOTAL 9 0 12 15 0.68 0 N/A 0.979 0.979 0.00 0.37 -1 1 11 2443 1 24 N/A 0.000 0.102 1.08 0.11 SR 0 11 1919 GALVANIZED STEEL 0.979 1.081 1.08 0.48 19 0 16 10 0.02 -0.03 1.03 0.387 0.387 0.35 0.02 9 0 15 509 1 24 0.31 0.000 0.003 1.12 0.07 SR 1 15 711 GALVANIZED STEEL 0.387 0.390 1.47 0.09 29 0 10 8 0.7 0.04 0 0.022 0.022 0.07 0.30 9 0 9 2215 1 26 0.06 0.000 0.056 1.09 0.09 SR 0 10 1208 GALVANIZED STEEL 0.022 0.079 1.16 0.40 39 0 16 9 0.02 -0.03 1.03 0.320 0.320 0.35 0.02 29 0 15 511 1 24 0.31 0.000 0.002 1.13 0.06 SR 1 15 713 GALVANIZED STEEL 0.320 0.322 1.48 0.07 RUNOUT OUTPUT DATA: ------ LOSSES ----- SECT. SECT. CUMUL PRESS RUN# 45 DIA LEN L/100 REG. COEF1 FITNG DYNAM VEL P VELOC RQD.NC CON# 90 HEI VEL REF# GAU. COEF2 ADDL. FRIC. STAT. STAT. ACT.NC -SM- TOA WID CFM MAT. DESCRIPTION DYNAM TOTAL TOTAL TOTAL ORIF. 100 0 10 3 0.05 -0.03 1.7 0.027 0.027 0.35 0.02 35 19 0 9 605 1 26 N/A 0.000 0.002 1.15 0.03 35 EF 90 10 330 GALVANIZED STEEL 0.027 0.029 1.50 0.06 10 110 0 10 3 0.07 -0.04 1.7 0.027 0.027 0.34 0.03 35 19 0 9 699 1 26 N/A 0.000 0.002 1.16 0.03 30 EF 90 10 381 GALVANIZED STEEL 0.027 0.029 1.50 0.06 10 120 0 10 3 0.09 -0.06 2 0.032 0.032 0.33 0.04 35 39 0 9 803 1 26 N/A 0.000 0.003 1.19 0.00 30 EF 90 10 438 GALVANIZED STEEL 0.032 0.035 1.52 0.04 10 130 0 8 3 0.12 -0.02 0 0.001 0.001 0.33 0.04 35 39 0 7 788 1 26 0.07 0.000 0.004 1.16 0.03 30 EF 0 8 275 GALVANIZED STEEL 0.001 0.005 1.49 0.07 8 140 0 10 17 0.11 0.18 0.13 0.075 0.075 0.32 0.05 35 29 2 9 908 1 26 N/A 0.000 0.020 0.94 0.25 35 EF 0 10 495 GALVANIZED STEEL 0.075 0.095 1.25 0.30 8
******* DUCTSIZE DESIGN PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC ******* YOUR COMPANY NAME CITY, STATE SAMPLE RUN TODAY'S DATE PAGE 3 ************************** DUCTSIZE OUTPUT DATA ************************* SYSTEM OUTPUT SUMMARY: DESCRIPTION OF SIZING RUN: SAMPLE CALCULATION NUMBER OF ACTIVE TRUNKS: 4 NUMBER OF ACTIVE RUNOUTS: 5 TOTAL OUTLET FLOW (CFM): 1750 TOTAL OUTLET FLOW AFTER HEAT GAIN: 1919 SIZE OF LARGEST TRUNK: 16 SIZE OF SMALLEST TRUNK: 10 SIZE OF LARGEST RUNOUT: 10 SIZE OF SMALLEST RUNOUT: 8 MAX SP LOSS OCCURS IN ROUTE TO RUNOUT NO: 120 CUM. STATIC PRESS LOSS AT ABOVE RUNOUT: 1.19 AVAIL STATIC PRESS AT ABOVE RUNOUT: 0.00 SOUND REPORT: RUNOUT ATTENUATION CENTER FREQUENCY, Hz NUMBER REQUIREMENTS 63 125 250 500 1000 2000 4000 8000 NC 100 REQUIRED ATTENUATION: 24 27 30 32 29 28 27 25 35 ACTUAL ATTENUATION: 26 29 34 47 81 116 70 69 35 ADDTL. ATTENUATION: 0 0 0 0 0 0 0 0 110 REQUIRED ATTENUATION: 24 27 30 32 29 28 27 25 35 ACTUAL ATTENUATION: 29 32 37 50 84 119 73 72 30 ADDTL. ATTENUATION: 0 0 0 0 0 0 0 0 120 REQUIRED ATTENUATION: 24 27 30 32 29 28 27 25 35 ACTUAL ATTENUATION: 31 34 41 57 99 154 88 87 30 ADDTL. ATTENUATION: 0 0 0 0 0 0 0 0 130 REQUIRED ATTENUATION: 24 27 30 32 29 28 27 25 35 ACTUAL ATTENUATION: 33 36 43 58 99 154 88 87 30 ADDTL. ATTENUATION: 0 0 0 0 0 0 0 0 140 REQUIRED ATTENUATION: 24 27 30 32 29 28 27 25 35 ACTUAL ATTENUATION: 29 29 35 48 76 134 83 88 35 ADDTL. ATTENUATION: 0 0 0 0 0 0 0 0
******* DUCTSIZE DESIGN PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC ******* YOUR COMPANY NAME CITY, STATE SAMPLE RUN TODAY'S DATE PAGE 4 ************************** DUCTSIZE OUTPUT DATA ************************* MIXED DUCT COSTS: MATERIAL: 1 - GALVANIZED STEEL -SIZE-- -AREA- #45-EL #90-EL #FIR.D #WEYES #-TEES #-RED. #COUPL -LENGTH- WEIGHT WEIGHT WEIGHT WEIGHT WEIGHT WEIGHT WEIGHT WEIGHT MAT.REF. $MCOST $MCOST $MCOST $MCOST $MCOST $MCOST $MCOST $MCOST MAT-GAU. $LCOST $LCOST $LCOST $LCOST $LCOST $LCOST $LCOST $LCOST -------- $TCOST $TCOST $TCOST $TCOST $TCOST $TCOST $TCOST $TCOST 8 6 0 0 0 0 0 0 0 3 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1 1.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 10 68 0 2 0 0 0 0 0 26 61.3 0.0 11.8 0.0 0.0 0.0 0.0 0.0 1 20.4 0.0 133.0 0.0 0.0 0.0 0.0 0.0 26 52.0 0.0 43.6 0.0 0.0 0.0 0.0 0.0 72.4 0.0 176.6 0.0 0.0 0.0 0.0 0.0 9 x 10 25 0 0 0 0 1 0 0 8 22.8 0.0 0.0 0.0 0.0 5.9 0.0 0.0 1 7.6 0.0 0.0 0.0 0.0 66.5 0.0 0.0 26 16.0 0.0 0.0 0.0 0.0 21.8 0.0 0.0 23.6 0.0 0.0 0.0 0.0 88.3 0.0 0.0 GAUGE 100 0 2 0 0 1 0 0 26 89.7 0.0 11.8 0.0 0.0 5.9 0.0 0.0 SUB.TOT: 29.9 0.0 133.0 0.0 0.0 66.5 0.0 0.0 72.8 0.0 43.6 0.0 0.0 21.8 0.0 0.0 102.7 0.0 176.6 0.0 0.0 88.3 0.0 0.0 11 x 11 55 0 1 0 0 1 1 0 15 66.0 0.0 10.8 0.0 0.0 10.8 10.8 0.0 1 22.0 0.0 89.3 0.0 0.0 89.3 25.0 0.0 24 40.5 0.0 30.0 0.0 0.0 30.0 13.6 0.0 62.5 0.0 119.3 0.0 0.0 119.3 38.6 0.0 15 x 15 95 0 0 2 0 2 3 0 19 114.0 0.0 0.0 40.2 0.0 40.2 60.3 0.0 1 38.0 0.0 0.0 80.4 0.0 239.4 93.0 0.0 24 104.5 0.0 0.0 36.4 0.0 79.2 54.6 0.0 142.5 0.0 0.0 116.8 0.0 318.6 147.6 0.0 GAUGE 150 0 1 2 0 3 4 0 24 180.0 0.0 10.8 40.2 0.0 51.0 71.1 0.0 SUB.TOT: 60.0 0.0 89.3 80.4 0.0 328.7 118.0 0.0 145.0 0.0 30.0 36.4 0.0 109.2 68.2 0.0 205.0 0.0 119.3 116.8 0.0 437.9 186.2 0.0 AREA/QTY: 250 0 3 2 0 4 4 0 TOT.LBS: 269.7 0.0 22.6 40.2 0.0 56.9 71.1 0.0 $MCOST: 89.9 0.0 222.3 80.4 0.0 395.2 118.0 0.0 $LCOST: 217.8 0.0 73.6 36.4 0.0 131.0 68.2 0.0 $TOTAL: 307.7 0.0 295.9 116.8 0.0 526.2 186.2 0.0 MIXED DUCT SUMMARY AREA/NUM WEIGHT $MCOST $LCOST $TCOST TOTAL DUCT: 250 270 90 218 308 TOTAL FITTING: 13 191 816 309 1,125 OVERALL TOTALS: 461 906 527 1,433